Moisture monitoring and fault location

pulsPG

TDR measurement

The pulsPG TDR monitoring unit, front viewAI generated
1–8 pipes
external measurement modules
8000 m
TDR range (PVF 0.90)
IP65
protection rating
GPRS / Ethernet
communication

Monitors moisture and locates the fault

The pulsPG is a localising monitoring module that uses TDR (Time Domain Reflectometry, pulse echometer) technology. It is used to monitor district heating and district cooling pipes and other pipelines, e.g. oil. The unit consists of a main unit and 1–8 external measurement modules, and the main unit can hold a maximum of two TDR measurement cards.

In addition to insulation resistance and galvanic voltage, the pulsPG measures the status of the pipe: the deviation of the TDR curve from the reference and, in case of damage, the distance to the fault. When a fault occurs, a TDR curve is saved for analysis.

The pulsPG alarms when the TDR curve deviates from the reference or the previous curve by more than the set limit, for example 0.5%. It also calculates a status code that tells the type of fault, and synchronises curves and readings to both the monitoring system and Stateview’s S-Plan. The Equalizer function shows small changes along the pipe over time. It helps locate moisture that reaches the leakage wire only locally, for example after heavy rain or in a pit.

  • Measuring modules are connected directly to the pipe without external cables.
  • With external measurement cards the main unit also collects data from separate buildings and chambers.
  • You pay only for the equipment you need, and the system is easy to adapt when the pipe network changes.
  • Monitoring and alarms via the monitoring system.
  • Proven and widely used TDR technology based on the Stateview measurement card. Fully compatible with Stateview System II.
  • As an option, the module runs the same analyses as the SM20 handheld instrument and saves data in the same databases, so an expert can support the analysis remotely.

How leakage wire monitoring works

TDR measurement
Range (PVF 0.90)8000 m
Measurement cardTDR for 2 leakage wires (loop)
Measurement
Insulation resistance0–65 MΩ
Loop resistance0–100 Ω
Galvanic voltage−1000…+1000 mV
Communication and power
CommunicationGPRS, Ethernet
Power supplyMains / battery
Voltage110–230 VAC / 15–30 VDC
Power30 W
Protection ratingIP65