District heating and cooling networks

Leakage wire monitoring

Together, the leakage wire, the measuring module and the alarm limits show whether there is moisture in the pipe insulation and where it comes from.

Principle

How the monitoring works

Two copper leakage wires (Nordic system, 1.5 mm²) run in the insulation of a pre-insulated district heating or district cooling pipe. The wires form a loop that the Pipeguard module measures automatically.

The module detects a moisture spread of just a few centimetres around the leakage wire over about 8 km of wire, or 4 km of pipe. It detects both leaks from inside the pipe and water entering the insulation from outside through the casing pipe.

Readings and alarms are shown in the monitoring system. A Fixbox measuring point makes handheld measurements easy and gives a stable earth point.

Two pre-insulated district heating pipes in an open trench on a Finnish residential street in autumnAI generated

Measurement methods

Loop resistance

0–100 Ω

Shows whether the loop is intact. If the leakage wire breaks, the module measures the wires from both directions and monitoring continues.

Insulation resistance

0–10 000 kΩ

Resistance between the leakage wire and the steel pipe. Above 10 000 kΩ in an intact pipe; moisture in the insulation lowers the value.

Galvanic voltage

0–1000 mV

0 mV in an intact pipe. The voltage tells whether the water is district heating water or comes from outside.

TDR measurement (pulsPG)

8000 m

Compares the TDR curve with the reference curve and, in case of damage, gives the distance to the fault.

Read more about pulsPG

Interpreting the readings

SituationInsulation resistanceGalvanic voltage
Intact pipeabove 10 000 kΩ0 mV
Joint or casing leak (groundwater from outside)fallsrises clearly more than with district heating water
Leak from the district heating pipe into the insulation (district heating water)fallsrises, but less than with water from outside
Short circuitshort circuit starts at 1–5 kΩ, finally 0falls to zero

Alarm levels

Green – normal, no alarm.
Orange – warning: the first alarm limit has been passed.
Red – the value has passed two alarm limits and is at a level that can damage the pipe.

The QPG summary alarm

QPG combines insulation resistance and galvanic voltage into one grade on a scale of 0–5. Find the insulation resistance level (row) and the galvanic voltage level (column). Each alarm limit passed raises the grade by one.

Insulation resistance ↓ / Galv. voltage →NormalHighHigh high
NormalQPG 0QPG 1QPG 2
LowQPG 1QPG 2QPG 3
LowLowQPG 2QPG 3QPG 4
Short circuit (1–5 kΩ)QPG 5QPG 5QPG 5
  • Overriding rule: when insulation resistance falls to the short-circuit level (1–5 kΩ), QPG is always 5 regardless of galvanic voltage.
  • QPG 1 is an early stage: one value has passed the first alarm limit.
  • QPG 5 means a short circuit: the values cannot fall any lower, and damage to the pipe has certainly started.

Recommended limits

Insulation resistance
LevelValueMeaning
Normalabove 10 000 kΩDry insulation. The value of a new, intact pipe.
Low (1st limit)200–500 kΩEarly sign of moisture.
LowLow (2nd limit)about 50 kΩThe insulation has clearly deteriorated.
Short circuit1–5 kΩBelow this level the loop is short-circuited. QPG always goes to 5.
Galvanic voltage
LevelValueMeaning
Normalabout 0 mVIntact pipe, no water in the insulation.
High (1st limit)about 50 mVDeviation detected.
High high (2nd limit)about 200 mVClear rise in voltage.

Limits are set per loop in the monitoring system. In new networks in good condition the Low limit can be set very high, e.g. 9 900 kΩ, so that deviations are detected as early as possible.

Installation, power and communication

Secure communication

The module’s SIM card is in a private APN, and all traffic runs in a VPN tunnel directly to the operator’s servers. A SIM card taken out of the module cannot connect to anything but Pipeguard modules. The same connection allows remote support and module updates.

Power supply

The microPG and miniPG tell from their supply voltage whether they run on battery or mains. On battery the module works in energy-saving mode; above 14.2 V it stays online all the time. A solar panel connects through a regulator, and a solar power tower is also available, with an optional 12 V fan to ventilate the chamber.

Location

If the signal is weak in the chamber or substation, the antenna is taken outside. Metal structures can block the connection completely, so test the place before installing permanently. At least two level switches can be connected to the modules.